subglobal1 link | subglobal1 link | subglobal1 link | subglobal1 link | subglobal1 link | subglobal1 link | subglobal1 link
subglobal2 link | subglobal2 link | subglobal2 link | subglobal2 link | subglobal2 link | subglobal2 link | subglobal2 link
subglobal3 link | subglobal3 link | subglobal3 link | subglobal3 link | subglobal3 link | subglobal3 link | subglobal3 link
subglobal4 link | subglobal4 link | subglobal4 link | subglobal4 link | subglobal4 link | subglobal4 link | subglobal4 link
subglobal5 link | subglobal5 link | subglobal5 link | subglobal5 link | subglobal5 link | subglobal5 link | subglobal5 link
subglobal6 link | subglobal6 link | subglobal6 link | subglobal6 link | subglobal6 link | subglobal6 link | subglobal6 link
subglobal7 link | subglobal7 link | subglobal7 link | subglobal7 link | subglobal7 link | subglobal7 link | subglobal7 link
subglobal8 link | subglobal8 link | subglobal8 link | subglobal8 link | subglobal8 link | subglobal8 link | subglobal8 link

 

CL4FIRE
Single Penetrations – Horizontal or Vertical
Concrete, Gypsum, Wood Floor / Gypsum Ceiling Assemblies

CL4-PHV/120-01
FTH Rating - 1 or 2 Hours

Tested to CAN/ULC-S115-95, ASTME-814, UL-1479

Rated for use with CL4FIRE Fire Protection Thermal Insulation Only – No Substitutes
Maximum Annular Space of 6"

Gypsum Wall

Gypsum Ceiling
   

Concrete Wall

Concrete Floor

1. Floor or Wall Assemblies:

  • Code conforming 1 or 2-hour floor or wall assembly. 
  • Minimum 4 ½" thick lightweight or normal weight concrete, 8" thick concrete block (filled or unfilled), 1 or 2 hour gypsum wall assembly with framed opening, 1- hour gypsum ceiling / wood floor assembly with framed opening.

2. Penetrating Item:

  • Rectangular or Round #26 gauge or thicker steel air duct or #16 gauge grease duct

3. Firestop System Component 1:

  • Minimum 4" thickness of CL4FIRE (blue) or CL4FIRE (red) fire protection thermal insulation, or mineral wool insulation tightly compressed  into concrete opening, recessed ¼" from the top and flush with the bottom of a gypsum ceiling / wood floor assembly, or recessed ¼" from both sides of a concrete or framed gypsum wall assembly. 

4. Firestop System Component 2:

  • Firestop Sealant installed a minimum of ¼" deep flush with the top surface of a floor assembly or both sides of a wall assembly. 
  • Installation can consist of one of the following listed caulking products:
    • HILTI - FS-1,  
    • A/D FIREBARRIER - Silicone Sealants
    • Passive Fire Protection Partners (PFP) - 4800 DW
    • TREMCO – Fyresil
    • 3M FB-1000 or FB-1003
    • NUCO Self Seal Silicone GG-200 or SL-100

5. Firestop System Component 3:  

  • Duct may be wrapped with CL4FIRE (blue) or CL4FIRE (red) insulation through the opening or alternately be installed on a bare duct with insulation firmly abutting both sides of firestop assembly.
  • NOTE: Grease ducts can only be installed with CL4FIRE (blue) abutting both sides of the firestop in concrete assemblies only.